Checking customer ground continuity with customer CB off (wired)
Procedure
- Prepare the multimeter to measure 1.0 V ac or less.
-
Measure the voltage on the female ground pin C (single-phase,
Figure 1) or "Ground" (three-phase, Figure 2) on each mainline power cable connector (at DC-UPS end) and building
ground.
Is the voltage less than 1.0 V ac?
- Yes, go to step 4.
- No, continue at the following step.
Figure 1. Single-phase mainline power connector at DC-UPS end 
Figure 2. Three-phase high voltage (380 - 415 V) mainline power connector at DC-UPS end 
-
Voltage is present at a customer outlet with the customer circuit breakers off.
DANGERInform the customer that even though the circuit breaker is off, voltage higher than 1.0 V ac is measured at the failing customer voltage outlet pins.
Do not continue until the voltage is less than 1.0 V ac.
- Prepare the multimeter to measure 1.0 ohm or less of resistance.
-
Measure the resistance between the female connector ground pin on each mainline power cable and
the building ground.
Is the resistance 1.0 ohm or less?
- Yes, continue with the next section.
- No, inform the customer. Do not continue until the resistance is 1.0 ohm or less.