Exchange the CEC enclosure PCIe four-port card
Before you begin
Use approved ESD procedures to prevent damage.
Attention:
- This procedure is not a stand-alone procedure. Customer disruption and damage to the hardware might occur when microcode and power boundaries are not in the proper conditions for this service action.
- If a serviceable event FRU repair directed you to this procedure, the microcode and power boundaries are already set.
- If a serviceable event FRU repair did not direct you to this procedure, see MAP1230 Replace a FRU without using a serviceable event.
Notes:
- All the cables and FRUs to be removed must be uniquely identified so they can be reinstalled correctly.
- If an installed earthquake resistance kit prevents you from accessing this FRU, refer to MAP1600.
Preparing the CEC enclosure to remove and replace the PCIe four-port card
Procedure
- Use a replacement part with a valid DS8000® part number to ensure it has the proper firmware, VPD, and/or configuration to ensure it is compatible with the DS8000 service procedures. Attempting to use a generic server FRU might fail and require next level of support to recover.
-
All parts being removed must be marked or identified so they can be installed into their
original locations.
Note: Failure to do this can extend the service duration and may require next level of support assistance.
- The management console keyboard can be moved between the operating and stowed position as needed to allow service clearance above the CEC enclosure.
-
Use the front and rear blue identify LEDs to determine the CEC enclosure to be repaired. Both
blue LEDs should be lit.
- CEC control panel blue identify LED
as shown in Figure 1. - CEC enclosure rear blue identify LED
as shown in Figure 2.
Note: If both the front and rear CEC enclosure identify LEDs are not lit, use the location code listed in the serviceable event FRU list. See MAP1245 Finding FRUs by using location codes.Figure 1. Control panel LEDs 
Figure 2. CEC enclosure rear LEDs 
- CEC control panel blue identify LED
-
Verify that the CEC enclosure is in the power-off state. See Figure 3.
- At the rear of the CEC enclosure, view all CEC enclosure power supply DC LEDs.
-
Are all DC (output) LEDs flashing?
- Yes, continue with the next step.
- No, do not continue with this FRU replacement. Go to MAP4841 CEC enclosure fails to power off during service processor repair (Models 961, 98x).
Figure 3. Location of the power supplies and LEDs (Models 980, 983, 984) 
- Use the flashing slot-identify LED to confirm the location of the adapter to be replaced.
-
Attach the electrostatic discharge (ESD) wrist strap.
Attention:
- Attach an electrostatic discharge (ESD) wrist strap to an unpainted metal surface of your hardware to prevent the electrostatic discharge from damaging your hardware.
- When using an ESD wrist strap, follow all electrical safety procedures. An ESD wrist strap is used for static control. It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment.
- If you do not have an ESD wrist strap, just prior to removing the product from ESD packaging and installing or replacing hardware, touch an unpainted metal surface of the system for a minimum of 5 seconds.
-
Disconnect the power cords
from the CEC with the DC
(output) LEDs flashing. See Figure 4.
Notes:- Ensure the power cords are correctly labeled.
- The power supply LEDs might continue to flash for up to 20 seconds while internal power is discharged.
- The power cord is fastened to the system using the hook-and-loop fastener
. Unstrap the fastener to allow
the enclosure to be placed in the service position.
Figure 4. Removing the power cords (Models 980, 983, 984) 
-
Observe the CEC enclosure control panel green power button LED
. See Figure 5.
- If it is off, go to the next step.
- If it is flashing, the CEC enclosure is still in the power-off state. DO NOT CONTINUE. Ensure that you have unplugged the power cables.
Figure 5. Control panel LEDs 
-
Disconnect all remaining cables from the rear of the CEC enclosure. See Table 1 and Figure 6.
Table 1. CEC enclosure cable connections Connection Description P1-T1 (HMC 1) FSP Ethernet P1-T2 (HMC 2) FSP Ethernet P1-C7-T1, P1-C7-T2, P1-C7-T3, P1-C7-T4 PCIe to I/O enclosures (2U) P1-C8-T1, P1-C8-T2 i2c to RPCs P1-C10-T1, P1-C10-T2 LPAR Ethernet P1-C10-T3, P1-C10-T4 Customer network (optional feature, if used) P1-C11-T1, P1-C11-T2
P1-C11-T3, P1-C11-T4Customer network (optional feature, if used) P1-C12-T1, P1-C12-T2 RS485 to RPCs Figure 6. CEC enclosure location codes (rear view) (Models 980 and 984) 
-
Remove the front cover.
- Ensure that you have the electrostatic discharge (ESD) wrist strap attached. If not, attach it now.
-
Remove the two shipping screws
(if present) that secure the
system to the rack.
- Pull the cover away from the system. The cover has an indentation where you can hold onto it more easily.
Figure 7. Removing the front cover 
-
Place the CEC enclosure into the service position.
-
Remove the front screws
(if present) that secure the
enclosure to the rack.
Figure 8. Removing the front screws 
-
Release the side latches
and pull the latches to slide
out the enclosure assembly.
Figure 9. Releasing the side latches 
-
Remove the front screws
-
Remove the service access cover.
- Ensure that you have the electrostatic discharge (ESD) wrist strap attached. If not, attach it now.
-
Release the latch by pushing the release latch
in the direction shown.
-
Slide the cover
off
the system unit. When the front of the service access cover has cleared the upper frame ledge, lift
the cover up and off the system unit.
Attention: For proper cooling and airflow, replace the cover before turning on the system.
Figure 10. Removing the service access cover 
-
Attach the electrostatic discharge (ESD) wrist strap. Your system has an ESD pin on the
backplane as shown in Figure 11. Attach the ESD wrist strap to the ESD
pin.
Attention:
- Attach an electrostatic discharge (ESD) wrist strap to an unpainted metal surface of your hardware to prevent the electrostatic discharge from damaging your hardware.
- When using an ESD wrist strap, follow all electrical safety procedures. An ESD wrist strap is used for static control. It does not increase or decrease your risk of receiving electric shock when using or working on electrical equipment.
- If you do not have an ESD wrist strap, just prior to removing the product from ESD packaging and installing or replacing hardware, touch an unpainted metal surface of the system for a minimum of 5 seconds.
Figure 11. Location of the ESD pin 
Removing the CEC enclosure PCIe four-port card
About this task
To remove the CEC enclosure PCIe four-port card, complete the following steps:
Procedure
- Ensure that you have the electrostatic discharge (ESD) wrist strap attached. If not, attach it now.
-
To set the adapter latch
at the target slot into the open
position, rotate the latch
on the rear of the system, in the direction shown in Figure 12.
-
Carefully grasp the adapter
by its top edge or tailstock,
and remove the adapter from the slot, as shown in Figure 12.
Attention: A pin on the tailstock of the adapter resembles a removable screw. Do not remove this pin. It is required for correct alignment and seating.Note: If adapter port filler plugs are present, note their locations and remove them. Retain the plugs for use with the new adapter.Figure 12. Removing a PCIe adapter from a rack-mounted system 
- Place the removed adapter on an approved ESD surface.
Replacing the CEC enclosure PCIe four-port card
About this task
To replace the CEC enclosure PCIe four-port card, complete the following steps:
Procedure
- Ensure that you have the electrostatic discharge (ESD) wrist strap attached. If not, attach it now.
-
If necessary, remove the adapter from the antistatic package.
Attention: Avoid touching the components and gold connectors on the adapter.
-
Place the adapter, component-side up, on a flat, antistatic surface.
Attention: A pin on the tailstock of the adapter resembles a removable screw. Do not remove this pin. It is required for correct alignment and seating.
-
If the adapter latch
at the target slot is not already in the open position, pull the latch into the open position by
rotating the latch outwards from its clip on the back of the system, as shown in Figure 13.
- Carefully grasp the adapter by its top edge or tailstock, and align the adapter with the slot and its connector on the system backplane, as shown in Figure 13.
- On the system, press the adapter firmly into its connector.
- If port filler plugs were removed from the old adapter, install them in the same port locations in the new adapter.
-
To lock the adapter in its slot, rotate the adapter latch
in the direction that is shown
in Figure 13.
Figure 13. Installing or replacing a PCIe adapter in a rack-mounted system 
Preparing the CEC enclosure for operation after removing and replacing the PCIe four-port card
About this task
To prepare the system for operation, complete the following steps:
Procedure
- Ensure that you have the electrostatic discharge (ESD) wrist strap attached. If not, attach it now.
-
Replace the service access cover.
-
Slide the cover
on
to the system unit.
-
Close the latch release
by pushing it in the direction
shown.
Figure 14. Installing the service access cover 
-
Slide the cover
- Ensure that you have the electrostatic discharge (ESD) wrist strap attached. If not, attach it now.
-
Place the CEC enclosure into the operating position.
- Ensure that you have the electrostatic discharge (ESD) wrist strap attached. If not, attach it now.
-
Unlock the blue rail safety latches
by lifting them upward.
-
Push the system unit
back into the rack until both system unit release latches lock into position.
- Secure the enclosure to the rack with screws, if screws were removed when preparing the enclosure for service.
Figure 15. Placing the CEC enclosure into the operating position 
-
Replace the front cover.
- Slide the cover onto the system.
- Close the release latches by pushing in the direction as shown in Figure 16. The cover snaps into place and has an indentation where you can hold onto it more easily.
-
Replace the shipping screws
.
Figure 16. Installing the front cover 
- Attach the electrostatic discharge (ESD) wrist strap.
-
Reconnect all cables, except for power cords. See Table 2 and Figure 17.
If optical Ethernet connections are used, use proper cleaning procedures.Important: The optical cable plugs (LC connectors) and ports (SFPs) must be cleaned before connecting them. Use cleaning tool 54Y4392 or IBM-approved alternative. After cleaning SFPs with the tool, use air bulb 45D2645 or IBM-approved alternative. For detailed procedures, refer to current DS8000 Info Alerts or contact your next level of support.
Table 2. CEC enclosure cable connections Connection Description P1-T1 (HMC 1) FSP Ethernet P1-T2 (HMC 2) FSP Ethernet P1-C7-T1, P1-C7-T2, P1-C7-T3, P1-C7-T4 PCIe to I/O enclosures (2U) P1-C8-T1, P1-C8-T2 i2c to RPCs P1-C10-T1, P1-C10-T2 LPAR Ethernet P1-C10-T3, P1-C10-T4 Customer network (optional feature, if used) P1-C11-T1, P1-C11-T2
P1-C11-T3, P1-C11-T4Customer network (optional feature, if used) P1-C12-T1, P1-C12-T2 RS485 to RPCs Figure 17. CEC enclosure location codes (rear view) (Models 980 and 984) 
-
Reconnect the power cords
to the CEC enclosure. See Figure 18.
-
Fasten the power cords to the enclosure using the hook-and-loop fasteners
.
Figure 18. Connecting the power cords 
-
Verify the CEC enclosure has power available. See Figure 19.
- At the rear of the CEC enclosure, view the CEC enclosure power supply DC LEDs.
-
Are all DC (output) LEDs flashing?
- Yes, continue with the next step.
- No, ensure the power cords are properly connected. If no connection problem is found, contact your next level of support.
Figure 19. Location of the power supplies and LEDs (Models 980, 983, 984) 
-
Wait up to 5 minutes for the CEC enclosure control panel power button LED
to flash. See Figure 20.
Note: This ensures the CEC enclosure is in the power-off state.Is the power button LED flashing?
- Yes, go to the next step.
- No, ensure the CEC enclosure power supplies are fully seated. The possible failing FRUs are the CEC enclosure system backplane, I2C interface card and cables, and control panel. You can also call the next level of support.
Figure 20. Control panel LEDs 
- Close the rear door of the rack.
- Exit this service information center parts exchange procedure and return to the procedure that sent you here.